top of page

Feeder Protection Relays

Atlas Energy supplies HVEX feeder protection relays for medium-voltage feeder and transformer applications. Adjustable protection settings, local and remote control, programmable interlocking and event records support integration into the protection scheme specified for your installation.

Measurement and inputs

  • Four voltage inputs: 100 V AC or 100/√3 V AC nominal; measurement range 1–120 V.

  • Four current inputs: 1 A or 5 A nominal; measurement range 0.04–15 × In.

  • RMS voltage and current, active power, power factor and frequency measurement.

  • 50 Hz or 60 Hz versions; documented frequency ranges 45–55 Hz or 55–65 Hz.

Control, communications and records

  • 12 digital inputs and 5 digital outputs.

  • One RS485 port and one RS232 port.

  • IEC 60870-5-103 and Modbus RTU communications.

  • Storage for 200 sequence-of-events entries, 400 logs and 10 seconds of trip data.

  • Local/remote control, programmable interlocking and status/alarm/trip indicators.

Configuration and installation

Documented supply options are 220 V AC/DC ±20%, 110 V AC/DC ±20%, or 48 V DC ±20%, with consumption of 10 W or less. The specified operating environment is −10 to +55 °C (14 to 131 °F), 5–95% relative humidity without condensation, and altitude up to 4,000 m.

Provide the required protection functions, CT/VT secondary ratings, control voltage, trip-circuit requirements and communication protocol when requesting a quotation. The selected model and protection-function schedule must be confirmed for the project.

Download HVEX Medium-Voltage Feeder Protection Relay datasheet (English, PDF)

Request a Quote

    Discuss your project

    bottom of page