top of page

Transformer Turns Ratio Testers (TTR)

Technical documentation

Download HVEX Standalone Transformer Turns Ratio Tester datasheet (English, PDF)

Download HVEX Combined Winding Resistance and TTR Tester datasheet (English, PDF)

Request a QuoteTransformer turns ratio, phase displacement, and polarity testing. Atlas Energy supplies HVEX instruments for factory, commissioning, and maintenance tests on power, distribution, and instrument transformers. Choose a compact battery-powered TTR set or a combined instrument that also measures DC winding resistance.

Portable battery-powered TTR

The portable HVEX system measures turns ratio, phase angle, polarity, and excitation current. Automatic three-phase measurements support evaluation of ratio error, phase displacement, and tap information.

  • Turns-ratio measurement range: 0.8–10,000.

  • Published ratio accuracy: 0.1% from 0.9–200; 0.2% from 200–2,000; 0.3% from 2,000–10,000.

  • Published voltage accuracy: 0.05% on the HV side and 0.1% on the LV side.

  • Published phase-angle accuracy: 0.1°.

  • Internal battery; charger input: 100–240 V AC.

  • Dimensions: 320 × 240 × 130 mm (approximately 12.6 × 9.4 × 5.1 in).

  • Weight: 3 kg (approximately 6.6 lb).

Combined TTR and inductive winding-resistance instrument

This separate HVEX configuration combines ratio testing with resistance measurement for highly inductive windings. A touchscreen, proprietary software, and Ethernet connection support local and remote operation.

  • Supply: 110 V or 220 V, 60 Hz.

  • TTR test output: 220 V; documented voltage ratio: 200.

  • TTR uncertainty: typically 0.2%, maximum 0.5%.

  • Winding resistance, high-resistance range: 1 Ω–5 kΩ, using 250 mA and up to 130 V.

  • Winding resistance, low-resistance range: 100 µΩ–1 Ω, using 20 A and up to 2.5 V.

  • Winding-resistance uncertainty: typically 0.2%, maximum 1%.

  • Typical ramp time: 30 seconds for distribution-transformer winding-resistance tests; actual time depends on the specimen.

  • Weight: 20.2 kg (approximately 44.5 lb).

Applications and selection

Ratio, phase, and polarity measurements help identify incorrect connections, tap discrepancies, and abnormal winding behavior. The combined instrument adds DC winding-resistance data for a broader transformer assessment. Compare results with the transformer ratings, configuration, and applicable test criteria.

HVEX documentation references ABNT NBR 5356/5440 and IEC 60076; the portable TTR product page also references IEC 61869 and IEC 61010-1. Contact Atlas Energy with the transformer type, ratio range, required measurements, and available supply to select the appropriate HVEX model. The specifications above apply to their respective configurations.

    Discuss your project